Features |
MODELS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NLMNDBNT3EQ-2U15 |
NLMNDBNT3EQ-2U32 |
NLMNDBLT1P-2U15 |
NLMNDBLT1P-3U15 |
NLMNDBLT3P-3U15 |
NLMNDBNT1P-3U32 |
NLMNDBNT3P-3U32 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Can be used with 220V UPS with a maximum size of: |
4.4kVA |
7.5kVA |
4.4kVA |
4.4kVA |
4.4kVA |
7.5kVA |
7.5kVA |
Circuit breaker maximum current (A) at 220V |
15A |
32A |
15A |
15A |
15A |
32A |
32A |
19″ Rack mounting Cabinet space |
2U |
2U |
2U |
3U |
3U |
3U |
3U |
Surge Protection |
|
|
|
|
|
|
|
Integrated Surge Protector TYPE |
3 |
3 |
1+2 |
1+2 |
1+2 |
1+2 |
1+2 |
Surge Protection stages |
Single |
Single |
Single |
3 |
3 |
Single |
3 |
Automatic remote surge protection failure detection and failure indicator on protection module |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Power |
|
|
|
|
|
|
|
Power Sockets for air conditioners and NTU |
1x C19 Power Socket Optional 2x 3PinSA if no X21 interface present |
1x C19 Power Socket Optional 2x 3PinSA if no X21 interface present |
1x C19 Power Socket Optional 2x 3PinSA if no X21 interface present |
2x 3PinSA + 3x C19 Power Socket |
2x 3PinSA + 3x C19 Power Socket |
2x 3PinSA + 3x C19 Power Socket |
2x 3PinSA + 3x C19 Power Socket |
PDU’s – Rear Panel Mounted with Metering and remote switchable |
Single bank of 4 x C13 and 3 x C19 |
Single bank of 4 x C13 and 3 x C19 |
Single bank of 4 x C13 and 3 x C19 |
Dual Bank of 4 x C13 and 4 x C19 |
Dual Bank of 4 x C13 and 4 x C19 |
Dual Bank of 4 x C13 and 4 x C19 |
Dual Bank of 4 x C13 and 4 x C19 |
PDU Expansion C19 Expansion Connector. To Expand to a Choice of RS485 Controlled Optional PDU’s |
C19 Socket |
C19 Socket |
C19 Socket |
C19 Socket |
C19 Socket |
C19 Socket |
C19 Socket |
Power Feed to Cabinet – 3 Meter Cable on mounted plug directly into the unit |
Hubble Plug |
Hubble Plug |
Hubble Plug |
Hubble Plug |
Hubble Plug |
Hubble Plug |
Hubble Plug |
Power feed to UPS |
C19 Socket |
Cable mounted Hubble Socket |
C19 Socket |
Cable mounted Hubble Socket |
Cable mounted Hubble Socket |
Cable mounted Hubble Socket |
Cable mounted Hubble Socket |
Re-enter Power feed from UPS |
C20 Socket |
Cable mounted Hubble Socket |
C20 Socket |
Cable mounted Hubble Socket |
Cable mounted Hubble Socket |
Cable mounted Hubble Socket |
Cable mounted Hubble Socket |
The UPS feed to and from unit can be connected to manually bypass the UPS |
C20 to C19 Lead |
Hubble Socket to Plug |
C20 to C19 Lead |
Hubble Socket to Plug |
Hubble Socket to Plug |
Hubble Socket to Plug |
Hubble Socket to Plug |
Power Metered and Monitored with under/over voltage/current/consumption alarms – Setup and Alerts through SNMP/SMS |
Yes (1 Units Included) |
Yes (1 Units Included) |
Yes (1 Units Included) |
Yes (3 Units Included) |
Yes (3 Units Included) |
Yes (3 Units Included) |
Yes (3 Units Included) |
Manual and Remote unit mains ON/OFF – with reporting and set Via SNMP/SMS |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
UPS bypass mode : Manual, Local and Remote controllable – with Error reporting and set Via SNMP/SMS |
No |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Systems backup Battery, Battery Charger and Battery SoC Monitoring |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Earthing Stud |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
UPS |
|
|
|
|
|
|
|
Modbus Communication to UPS via either RS485 or RS232 |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
X.21 |
|
|
|
|
|
|
|
Slot for Up to 3 x X.21/V11 Optically Isolation Modules with Interface Present and Data Active Flow Control Monitoring and Error reporting Via SNMP/SMS |
Optional |
Optional |
Optional |
Optional |
Optional |
Yes |
Yes |
X21 Cable _DB15 Male to Female 1.5 Meter include |
Optional |
Optional |
Optional |
Optional |
Optional |
Yes |
Yes |
Environmental monitoring |
|
|
|
|
|
|
|
1 Wire Temperature Sensors – 2 x Temperature (expandable to 8 units) with Error reporting Via SNMP /SMS |
Yes (2 Units Included) |
Yes (2 Units Included) |
Yes (2 Units Included) |
Yes (2 Units Included) |
Yes (2 Units Included) |
Yes (2 Units Included) |
Yes (2 Units Included) |
Water Flooding/Leak Detection sensor with Error reporting Via SNMP/SMS |
Yes (2 Units Included) |
Yes (2 Units Included) |
Yes (2 Units Included) |
Yes (2 Units Included) |
Yes (2 Units Included) |
Yes (2 Units Included) |
Yes (2 Units Included) |
Humdity sensor with Error reporting Via SNMP/SMS |
Optional |
Optional |
Optional |
Optional |
Optional |
Optional |
Optional |
Access Control |
|
|
|
|
|
|
|
Door Maglock/Actuator set control Interface with Battery Backup |
3 x 12VDC feeding Output |
3 x 12VDC feeding Output |
3 x 12VDC feeding Output |
3 x 12VDC feeding Output |
3 x 12VDC feeding Output |
3 x 12VDC feeding Output |
3 x 12VDC feeding Output |
Wiegand Access control |
1 x Wiegand Interface and 125kHz keypad and proximity card reader |
1 x Wiegand Interface and 125kHz keypad and proximity card reader |
1 x Wiegand Interface and 125kHz keypad and proximity card reader |
1 x Wiegand Interface and 125kHz keypad and proximity card reader |
1 x Wiegand Interface and 125kHz keypad and proximity card reader |
1 x Wiegand Interface and 125kHz keypad and proximity card reader |
1 x Wiegand Interface and 125kHz keypad and proximity card reader |
Door switches to Monitor the Front/Rear/Side Door of cabinets |
3 included |
3 included |
3 included |
3 included |
3 included |
3 included |
3 included |
Fire protection |
|
|
|
|
|
|
|
Fire extinguisher controller port (Current loop) |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
Smoke detector input NO and NC |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
Air Conditioner |
|
|
|
|
|
|
|
Air Conditioner Control Interface |
1 X Input STATE and 1 Output ON/OFF |
1 X Input STATE and 1 Output ON/OFF |
1 X Input STATE and 1 Output ON/OFF |
1 X Input STATE and 1 Output ON/OFF |
1 X Input STATE and 1 Output ON/OFF |
1 X Input STATE and 1 Output ON/OFF |
1 X Input STATE and 1 Output ON/OFF |
Networking and remote monitoring |
|
|
|
|
|
|
|
10/100BaseT networking port with SNMP – (5 Meter Patch lead Included) |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
DHCP Default Network configuration |
DHCP enabled |
DHCP enabled |
DHCP enabled |
DHCP enabled |
DHCP enabled |
DHCP enabled |
DHCP enabled |
Centralized monitoring with SNMP – 4 Programmable Destinations IP addresses |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Remote Power monitoring, control and configuration with SNMP |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Remote Environmental monitoring, control and configuration with SNMP |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Remote Access monitoring, control and configuration with SNMP |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Display |
|
|
|
|
|
|
|
Local Alarm Indication on Full Colour LCD |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
WEB Number, Site address Detail and Unit Serial Numbers configuration through SNMP – LCD displayed |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
GSM |
|
|
|
|
|
|
|
GSM Modem with Conditional SMS Alerting and Configuration |
Optional |
Optional |
Optional |
Optional |
Optional |
Optional |
Optional |
Power cords |
|
|
|
|
|
|
|
C20 to C19 power cords 1.5 to 1.8M (IEC 60320) |
None |
None |
4 |
4 |
2 |
2 |
2 |
C13 to C14 power cords 1.5 to 1.8M (IEC 60320) |
None |
None |
2 |
2 |
4 |
4 |
4 |
|
|
|
|
|
|
|
|
Warranty |
Life Time |
Life Time |
Life Time |
Life Time |
Life Time |
Life Time |
Life Time |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Optional PDU’s |
|
|
|
|
|
|
|
RS485 MB Monitored and Metered PDU C20 Pluggable – 1U Rack mountable with 4 X C19 Sockets and 8 X C13 Sockets |
Optional |
Optional |
Optional |
Optional |
Optional |
Optional |
Optional |
RS485 MB Monitored and Metered PDU C20 Pluggable – 1U Rack mountable with 4 X C15 Sockets and 8 X C13 Sockets |
Optional |
Optional |
Optional |
Optional |
Optional |
Optional |
Optional |
RS485 MB Monitored and Metered PDU C20 Pluggable – 1U Rack mountable with 4 x 3 Prong SA Standard Sockets. |
Optional |
Optional |
Optional |
Optional |
Optional |
Optional |
Optional |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Additional Optional Devices |
|
|
|
|
|
|
|
Temperature sensors (1-Wire) |
Optional |
Optional |
Optional |
Optional |
Optional |
Optional |
Optional |
Humidity sensors |
Optional |
Optional |
Optional |
Optional |
Optional |
Optional |
Optional |
Rope Flooding Sensors |
Optional |
Optional |
Optional |
Optional |
Optional |
Optional |
Optional |
Smoke detectors |
Optional |
Optional |
Optional |
Optional |
Optional |
Optional |
Optional |
Smother fire extinguisher |
Optional |
Optional |
Optional |
Optional |
Optional |
Optional |
Optional |